Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM05124
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/01/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 09/05/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | 1. The Watts SD-2 dual check valve is not recognized as a backflow prevention assembly because it is not testable (see Section 603.2.4, UPC 2003). Appliances (e.g. coffee brewer, commercial ice maker, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps require backflow prevention. Reference Sections 602.3, 603.0, and Table 6-2, UPC 2003. 2. The Plumbing connection schedule on sheet K-102 is not legible. Note: Backflow preventor changed to an approved double-check valve and sheet K-102 replaced, 9/7/06. |
| 09/05/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/08/2006 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/10/2006 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 10/10/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |