Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM05124
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/12/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/12/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Fan-coil AC-15 is scheduled to provide make up air for the kitchen hood. Provide information from the manufacturer to show that the unit can successfully operate with 100% outside air greater than 90 degrees Fahrenheit. Reference Section 304.1, IMC 2000. |
| 07/12/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the construction details for the trench drain in the laundry (Room 151), for the architectural (details 11 & 10/A8.2) and plumbing (detail 1/P4.3). Clarify the connection to the washer/extractor and the "drying machine". How are the drains trapped? Reference Section 103.2.3, UPC 2003. 2. Appliances (e.g. coffee brewer, commercial ice maker, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps require backflow prevention. Reference Sections 602.3, 603.0, and Table 6-2, UPC 2003. |
| 07/24/2006 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 07/27/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide GFCI protection for Elevator Equipment room per NEC 620.85. This was done for one such receptacle in Room 251, but not the other. 2. Sheet E6.3 SB MSB1 size the EGC for Panel L1P. 3. Provide power for AC-15 and CU-15, as specified on Sheet M5.1, Mechanical Revision #4, 5/31/06. 4. Lumen calculations on Sheet E6.6 contain the following errors: Total Mean Lumens for Fixture D19 appears to be 23,760, not 11,880; Total Mean Lumens for Fixture D20 appears to be 6650, not 3325; Total Mean Lumens for entire property appears to be 693,610, not 678,405; Total Mean Lumens for unshielded component appears to be 54,310, not 39,105. The site still appears to be in compliance, but margins are slimmer such that it justifies the above corrections. 5. Electrical Plans Examiner has noticed that a Fire Pump and Jockey Pump have been called out on Sheet FP1.2. Please note that if this is the intent, such items shall be included in the Electrical design, and shall meet all requirements of NEC Article 695. |
| 08/02/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide the roof and floor diaphragm calc`s. Your response sheet specifies to see calc`s but did not find them. 2) Sheets 62 and 63 specify asterics at edge of table. Which indicate that the allowable values have been exceeded. What has been done to resolve this issue? 3) Specify on plans the space between spickets(rails), they shall not exceed 4" max. SEC.1012.3 |
| 08/03/2006 | GERRY KOZIOL | WWM | REVIEW | Denied | cannot drain /backwash pool into public sewer. needs manhole construction permit |
| 08/16/2006 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/24/2006 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 08/24/2006 | SUE REEVES | REJECT SHELF | Completed |