Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T05CM05124
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/01/2006 | ANDREW CONNOR | NPPO | REVIEW | Approved | Plans are not located on review shelf. |
| 03/01/2006 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1. Canopy Tree: A woody plant, other than a palm tree, with a mature crown diameter of at least fifteen (15) feet and having a trunk that, at maturity, is kept clear of leaves and branches at least six (6) feet above grade. Palms can not be considered canopy trees, revise landscape plan to include additional canopy trees within vehicle use area to the north. |
| 03/07/2006 | PETER MCLAUGHLIN | ZONING HC SITE | REVIEW | Approved | |
| 03/07/2006 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | 1. Revise bicycle parking calc. to be based on the number of veheicle parking spaces provided rather than the number required. LUC 3.3.3.5 2. The square footages in the F.A.R. calc. (general note 7) do not match with those shown on the drawing. Revise to be consistent. |
| 03/10/2006 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | March 10, 2006 TO: Bruce Call. AECM SUBJECT: Site Plan: Marriott Residence Inn - Airport REVIEWER: Loren Makus ACTIVITY NUMBER: T05CM05124 SUMMARY: The Site Plan and Drainage Report were reviewed by Development Services Department, Engineering Division on December 2, 2005. The Site Plan and Drainage Report were approved at this time. Note that the infiltration test results previously requested must be provided before the grading plan will be approved. If you have any questions or if you wish to discuss any of these comments, I can be reached at 520.791-5550 ext. 1161 or by email at loren.makus@tucsonaz.gov. Loren Makus, E.I.T. Senior Engineering Associate Engineering Division Development Services |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/24/2006 | GBONILL1 | APPROVAL SHELF | Completed |
| 03/24/2006 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 03/24/2006 | GBONILL1 | REJECT SHELF | Completed |