Permit Number: T05CM05121
Parcel: 12810082B

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T05CM05121
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE VICINITY MAP WITH STREETS LOCATED.
2) PROVIDE A FULL BUILDING LAYOUT SHOWING EXISTING TENANT LOCATIONS.
3) PROVIDE ACCESSIBLE RESTROOM PER THE ANSI A117.1 2003 OR PROVIDE BUDGET SHOWING 20% COST OS CONSTRUCTION IS BEING SPENT TOWARDS MEETING ACCESSIBILITY REQUIREMENTS.
4)CLARIFY WHAT THE STAIRWAY SHOWN IS FOR.
5) CLARIFY SEPERATED OR NONSEPERATED USE.
6) COMPLETE CODE ANALYSIS FOR JUSTIFICATION OF ALLOWABLE SQ. FOOTAGE.
10/10/2005 JIM EGAN FIRE REVIEW Approved
10/10/2005 LOREN MAKUS ENGINEERING REVIEW Approved
10/26/2005 DROBEY1 ZONING REVIEW Needs Review