Permit Number: T05CM05117
Parcel: 11306179A

Address:
3232 N WILSON AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM05117
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2005 GERRY KOZIOL WWM REVIEW Approved
11/28/2005 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T05CM05117

11/30/05 3732 N. WILSON AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. PROVIDE THE GAS METER AND GAS LINES LOCATION.

2. PLEASE PROVIDE THE SIZE OF THE EXISTING WATER METER AND THE SIZE OF THE WATER LINE TO THE "T" SUPPLYING THE GARAGE.

FOUNDATION PLANS:

1. DETAIL 2 / 2 IS USED TO DESCRIBE A FOOTING BUT DOESN'T APPEAR TO BE PROVIDED. PLEASE PROVIDE, OR IS THIS A "TYPO"?

FLOOR PLANS:

1. IS THE 3010 XO OVER THE SHOWER REQUIRED TO BE SAFETY GLASS? SEE R3308.4 .

2. NOTE THAT THE SHOWER ENCLOSURE SHALL BE FINISHED WITH CERAMIC TILE OR A
LISTED ENCLOSURE TO A HEIGHT OF 72" ABOVE THE DRAIN PER R307.2

STRUCTURAL PLANS:

1. ROOF LOADING DESIGN CRITERIA / 3 ; THE VALUES USED DIFFER FROM THE TRUSS DATA SHEETS.

SECTIONS - DETAILS - MISC. NOTES:

1. SHEAR WALL NOTES / 2,3 ; SIMPSON LISTS THEIR "HD5A" WITH MACHINE BOLTS. PLEASE JUSTIFY THE LAG BOLTS.

2. GENERAL NOTE 1 / 2 ; I.C.B.O. #1218 IS A REPORT FOR A RIDGE VENT. I CAN'T FIND #1218-0072. PLEASE HELP.

3. GENERAL NOTE 2 / 2 ; PLEASE UPDATE THE 2000 IRC TO THE 2003.

4. GENERAL NOTE 4 / 2 ; HOW DOES THIS APPLY TO THIS PROJECT ?

5. SECTION / 3 ; 1, 10 / 4 ARE THESE THE CORRECT DETAILS ? PLEASE PROVIDE THEM.

6. PLEASE PROVIDE A DETAIL TO TRANSFER THE SHEAR FROM THR WALL TO THE ROOF SHEATHING.

7. SHEAR WALL NOTE #1 / 2, 3 ; JUSTIFY THE 6d NAILS.

8. SHEAR WALL NOTE #5 / 2, 3 ; WHERE ARE SHEAR WALLS #6 AND #7 ?

9. SHEAR WALL SCHEDULE / 3 ; DO YOU WANT TWO ANCHOR BOLTS @ 32" O.C. ?

PLUMBING PLANS:

1. THE INTERIOR WATER DISTRIBUTION SYSTEM APPEARS TO BE UNDER SIZED. PLEASE JUSTIFY.

2. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF
EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE
APPLIANCE ON THE SYSTEM PER UPC 1217.2

3. PLEASE PROVIDE THE WATER FIXTURE UNITS FOR EXISTING RESIDENCE #1. ARE THOSE THE FIXTURE UNITS FOR EXISTING RESIDENCE #2 ON SHEET 5 ?

4. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE. PLEASE CHECK THE VALUES USED ON YOUR PLANS.

5. PLEASE PROVIDE AND SIZE THE COMBUSTION AIR FOR THE WATER HEATER.

ELECTRICAL PLANS:

1. PLEASE RE-CONSIDER THE 60 AMP SUB-PANEL. THE LOAD CALCULATIONS REQUIRE AT LEAST 69 AMPS.

2. THE NOTE UNDER THE 60 AMP SUB-PANEL MENTIONS A 100 AMP MAIN BREAKER WHICH WOULD EXCEED THE PANELS CAPACITY.

3. CIRCUIT 21/23 IN THE MAIN PANEL IS A 100 AMP CIRCUIT FEEDING A 60 AMP SUB-PANEL WITH A #4 CONDUCTOR. PLEASE RE-CONSIDER THIS.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2005 GBONILL1 OUT TO CUSTOMER Completed
12/02/2005 SUE REEVES REJECT SHELF Completed