Permit Number: T05CM05115
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T05CM05115
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2006 DMANN1 FIRE REVIEW Denied Submit site plan. Indicate location of underground fire sprinkler piping and fire protection piping to be relocated /removed prior to starting foundation. Provide approved fire protection water plan. Provide note on plan: " Fire protection piping and fire sprinklers shall remain in-service throughtout demolition/construction."
03/17/2006 PATRICIA GEHLEN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/17/2006 CINDY AGUILAR APPROVAL SHELF Completed
03/17/2006 CINDY AGUILAR OUT TO CUSTOMER Completed