Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM05115
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T05CM05115
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2005 JIM EGAN FIRE REVIEW Denied Submit site plan. Indicate location of underground fire sprinkler piping and fire protection piping to be relocated /removed prior to starting foundation. Provide approved fire protection water plan. Provide note on plan: " Fire protection piping and fire sprinklers shall remain in-service throughtout demolition/construction."
12/08/2005 RBABBIT1 LANDFILL REVIEW Approved