Permit Number: T05CM05112
Parcel: 12110005D

Address:
4730 E GRANT RD

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM05112
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2006 JWILLIA5 BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY / JUSTIFY THERE ARE ENOUGH RESTROOM FACILITIES SINCE THE EXISTING FACILITIES HAVE BEEN REMOVED. PROVIDE A FLOOR PLAN SHOWING THE WHOLE SUITE TO VIEW FOR EXITING AND DISTANCES TRAVELED. INCLUDE TOTAL SQ. FOOTAGE FOR THE COMBINED SUITES. PROVIDE CLARIFICATION ON CONSTRUCTION DOCUMENTS 8 1/2 X 11 IS NOT ACCEPTABLE. SEE ADDRESSING FOR SUITE NUMBER FOR A NEW C OF O. IT APPEARS 3 WATER CLOSETS ARE NEEDED FOR EACH SEX.
2) CLARIFY THAT OPENINGS INTO NEIGHBORING SUITES ARE ON BEARING OR NON-BEARING WALLS. IF BEARING WALLS PROVIDE STRUCTURAL CALCULATIONS.