Review Details: RESUBMITTAL - SITE ALL
Permit Number - T05CM05080
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2006 | DAVE MANN | FIRE | REVIEW | Denied | Show that sprinklers are required on site plan in LP2A set. Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy including any special hazards. 2. The design standard to be used. 3. The availability and adequacy of the water supply. 4. The design density and the area of operation. |
| 07/18/2006 | JMORALE1 | NPPO | REVIEW | Needs Review | |
| 07/18/2006 | JMORALE1 | LANDSCAPE | REVIEW | Needs Review | |
| 07/18/2006 | JMORALE1 | ZONING HC SITE | REVIEW | Needs Review | |
| 07/18/2006 | JMORALE1 | ZONING | REVIEW | Needs Review | |
| 07/18/2006 | JMORALE1 | ENGINEERING | REVIEW | Needs Review |