Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05044
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
10/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
10/05/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/07/2005 | DAVID RIVERA | ZONING | REVIEW | Approved | |
10/07/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
10/11/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/11/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
10/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05044 10/11/05 1. Provide description for new restroom fixtures. 2. Indicate panel and circuit for New Workroom and New Office Area fixtures, and all others which would apply. 3. New Circuit A-16 appears to have 720 VA, not 400. 4. Keynote 3 is used twice. Please clarify. |