Review Details: COMMERCIAL TI

Permit Number - T05CM05044
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2005 JIM EGAN FIRE REVIEW Approved
10/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/05/2005 ROBERT SHERRY WATER REVIEW Approved
10/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/07/2005 DAVID RIVERA ZONING REVIEW Approved
10/07/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/11/2005 GERRY KOZIOL WWM REVIEW Approved
10/11/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Needs Review
10/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05044 10/11/05

1. Provide description for new restroom fixtures.
2. Indicate panel and circuit for New Workroom and New Office Area fixtures, and all others which would apply.
3. New Circuit A-16 appears to have 720 VA, not 400.
4. Keynote 3 is used twice. Please clarify.