Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04957
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/28/2005 | JIM EGAN | FIRE | REVIEW | Denied | The building does not contain an existing fire sprinkler system. If a new fire sprinkler system is to provided as a part of this T.I., provide complete fire sprinkler system design criteria on plans. If the system is not to be provided at this time, correct code review checklist and remove note on sheet MP1. |
| 09/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/28/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM04957 DENIED 9/28/05 1. HP-1 has 208V electrical power, but is specified as 460/3/60 on Packaged Heat Pump Schedule Sheet MP1. Coordinate with Mechanical and clarify. 2. Please remove the redundant ground referenced in Keynote 5 on the line diagram. Reference NEC250.24 (B). |
| 09/28/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The use of ASHRAE 62n for ventilation calculations has not yet been adopted by the COT. Calculate the ventilation using Section 403, IMC 2000 or submit an appeal to the building official. |
| 09/29/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) pROVIDE CLEAR FLOOR SPACE ENVELOPES FOR EACH FIXTURE PER ANSI A117.1 2003. 2) PROVIDE HARD NONABSORBENT MATERIAL IN RESTROOM PER SECTION 1210 OF IBC 2003. 3) PROVIDE WALL SECTION WITH LATERAL BRACING PER SECTION 1621.1.2. |
| 10/10/2005 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 10/10/2005 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 10/10/2005 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |