Permit Number: T05CM04948
Parcel: 106070030

Review Status: Completed

Review Details: SITE

Permit Number - T05CM04948
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2005 DAN CASTRO ZONING REVIEW Approved
10/24/2005 DAN CASTRO ZONING HC SITE REVIEW Approved
11/03/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: November 3, 2005
ACTIVITY NUMBER: T05CM04948
PROJECT NAME: Jacob's Park Dog Area
PROJECT ADDRESS: 3300 North Fairview Ave.
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN, SWPPP


1. Include on the site plan estimated cut and fill quantities. It is acknowledged that cut and fill quantities are balanced. Cut and fill quantities are a requirement of DS 2-01. Site Plan Content. Include quantities on the site plan. DS 2-02.2.1.A.17.

2. Stormwater must be accepted and released from developments essentially at the same locations, and with the same magnitudes, as encountered under natural or existing conditions. Because grades have not been submitted on the site plan it is difficult to determine if the current drainage is being changed. Provide existing and proposed spot elevations. DS 2-01.16.

3. Handicap curb access ramps are required to be constructed with truncated domes, per recent a Federal ADA requirement. Show a detail or add a general note to the site plan indicating all public and private handicap curb access ramps will have truncated domes.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2005 GBONILL1 OUT TO CUSTOMER Completed
11/08/2005 SUE REEVES REJECT SHELF Completed