Permit Number: T05CM04943
Parcel: 123070510

Address:
1347 N PLUMER AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T05CM04943
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2005 DAN CASTRO ZONING REVIEW Denied COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The width of the perimeter yard is the distance measured horizontally from the property line to the face of each exterior building wall at the wall's highest point. Please dimension the perimeter yard from the west property line to the face of the refrigerator building wall and to the face of the great room building wall. (see redline drawing). (LUC 3.2.6.3) (LUC 3.2.6.4 Perimeter Yard "AA)

2. Revise exterior building wall heights listed on sheet 1 to be measured from design grade to the top of the parapet wall. In addition, label and dimension the heights on the elevation drawings from design grade to the highest point of the exterior building wall.

3. Per LUC Sec. 3.2.6.5.A, a minimum 10 foot wide perimeter yard is required along the east property line and measured from the face of the exterior building wall to the east property line. The plan currently shows a six foot four and one-half inch (6' 4 ½") perimeter yard from the garage to the east (street) property line.

4. Review of this plan by the Zoning Review Section may be done over the counter. Please contact Dan Castro to set an appointment.


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180. An appointment is required to discuss these comments in person.
10/28/2005 GERRY KOZIOL WWM REVIEW Approved NO CLEAR EXSISTINGFLOOR PLAN OR DEMO DRAWINGS- NO PLUMBING DRAWINGS. NO WAY TO ESTABLISH EXSISTING FIXTURES FOR CREDIT. NEED DRAWING SHOWING WHAT CURRENTLY EXSISTS VS NEW
11/07/2005 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T05CM04943

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FOUNDATION PLANS:

1. Provide consistent soil bearing pressure values for both the Concrete Note sheet 2 and the Structural Design Criteria sheets 3 & 5.
2. Revise the Structural Design Criteria Note sheet 3 showing the 2003 IRC.
3. Identify/detail the darkened area projecting from the basement east wall, sheets 2 & 3.
4. All exterior doors require a landing or floor at the exterior. Landings must be at least as wide as the doors they serve and 36" in the direction of travel, R311.4.3.

FLOOR PLANS:

1. Revise Floor Plan Keynote #11 sheet #3 to reference section 313 rather than 317.
2. One exit door shall be side hinged not less than 3' wide, R311.4.2. The landing at this exit door shall not be more than 1.5" lower than the top of the threshold R311.4.3.
3. Show the location of tempered glass within 24" of doorways (R308.4) at the Great Room window near the exterior doorway.
4. The walls and soffit of the enclosed space under stairs shall be protected on the enclosed side with ½" gypsum board, R311.2.2
5. Show that each water closet is located in a clear space not less than 30" wide (centered 15" from finished wall or fixture) and has a clear space in front not less than 21", IRC figure R307.2. The new Lav. water closet may not comply.

STRUCTURAL PLANS:

1. Specify TJI manufacturer and series. Show the load bearing conditions at the Garage/New Bath wall if necessary for the 24" o.c. spacing area.
2. Specify or detail the connection/supports for steel beams.
3. Show details for typical non-bearing conditions (floor and rafter/joist connections & gaps).

ELEVATIONS:

1. Provide complete drawings of all elevations including fireplaces and stairways. Provide stairway connection details and stringer sizes. Show fireplace hearth size and materials, R1003.10 or R1004.2. Provide fireplace cut sheets, make, model number and the approval number of the UL-127 testing agency (IE: ICBO #) for factory built (zero clearance) fireplaces, R1002, or note the requirement for deferred submittal to building inspector at installation.
2. Correct the plan notation and provide details for winder tread stairway rather than a spiral stairway, R311.5.3.2.
3. Note the size all roofing drains and scuppers on flat roofed areas, R903.4.
4. Calculate of attic space ventilation area using the correct attic area in compliance with R806.2. Note size and location of all vents needed to comply.
5. Note and dimension the fireplace chimney shall terminate a minimum of 2' above any point of roof within 10' measured horizontally and not less than 3' above the point where the chimney passes through the roof, R1001.6.

SECTIONS - DETAILS - MISC. NOTES:

1. Cross-sections shall be cross-referenced to the floor plan and framing plans (F-6, F-7, 1/5, 3/5) sheet 2. Clarify the location of framed and CMU walls.
2. Note or detail untreated exterior wood siding, sheathing and wall framing shall have a 6" clearance above the ground, R319.1 (5).
3. Ceiling gypsum board shall be either 5/8" or ½" sag resistant when applied to 24" o/c framing, IRC table R702.3.5 footnote d.

PLUMBING PLANS:

1. The City of Tucson has adopted the 1994 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). All plans must reference this code.
2. Clarify the future basement rough-in (water-closet and furnace or lav.) fixtures. Provide an isometric drawing of waste lines serving the basement area showing the size of waste lines, vents and stub-outs to future pumping equipment.
3. Provide the total fixture unit demand for the entire property per 1994 UPC Table 6-3.
4. Provide the maximum developed length of water line and diameter using 1994 UPC Table 6-4 assuming 46 to 60 psi using appropriate factoring for the pex system.
5. Clarify the existing 1-1/4" gas pipe note that appears on the high-pressure gas line to the meter, sheet 2B.
6. Clarify the location where the new 1-1/2" water pipe connects to the existing water line or meter. Clarify if the existing 1-1/2" water pipe serves the entire dwelling or only the existing portion, sheet 2B.
7. Note on plan compliance with the water conservation requirements. Water closets, 1.6 gallons per flush, sinks and showerheads, 3 gallons per minute, State Amend. R4-48-104.
8. Note on plans that shower and tub / shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
9. Provide pressure and temperature relief valve at water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down, UPC 608.5.
10. Show the location of all hose bibs, and note requirement for backflow preventers, UPC 603.
11. Correct the existing house-plumbing note on, sheet 2 that references, sheet 3 rather than sheet 2B.

MECHANICAL PLANS:

1. Note on plans: Mechanical shall comply with 2003 IRC chapters 12 - 24.

ELECTRICAL PLANS:

1. Receptacle outlets shall be installed in habitable spaces so that no point along the wall (exclude door openings) is more than 6' from an outlet, E3801.2. Add a receptacle on the west side of the Great Room.
2. Note that two or more 2O AMP small appliance circuits shall be provided to serve all receptacles outlets in the kitchen, breakfast room and dining room. Such circuits shall have no other outlets such as for the laundry room, E3603.2 and E3801.3 through E3801.4.5.
3. Add the refrigerator and ovens to the panel schedule showing circuit ampacity, wire size, and circuit numbers, E3606.2.
4. Smoke alarms are required inside and outside each separate sleeping area, R313.1.1 and R313.1.2.
5. Show a switch for the new master water-closet exhaust fan, E3606.2, and any other new outlet locations.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf
2. Provide cut sheets of selected light fixtures and lamp wattage before installation.

MODEL ENERGY CODE:

1. Provide energy calculations per the 2000 IECC w/ local amendments (climate zone 4B, Pima County < 4000 ft, 2100 HDD) to support selected "R" values of insulation and "U" values of the windows and doors. http://www.energycodes.gov/rescheck/
2. All insulation values and notes shall be consistent on the REScheck report and section keynotes, sheet 6. Also, compliant values for the windows and doors should be shown on the plans.


If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2005 GBONILL1 OUT TO CUSTOMER Completed