Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04923
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 09/27/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/27/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/27/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/27/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/27/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 09/28/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/28/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM04923 9/27/05 1. Provide panel schedules for all new electrical loads. The intent is to determine loading of feeders and possibly electrical service. 2. Plot location of panel on plans. 3. Provide panel and circuit number for any new electrical loads for which this was not done. 4. Specify conduit and conductor size and type. |
| 09/28/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | Conforming Structure Old FUP 1040 El Cert sumbitted |