Permit Number: T05CM04911
Parcel: 11713038C

Address:
44 E BROADWAY BL

Review Status: Active

Review Details: REVISION - - 4TH

Permit Number - T05CM04911
Review Name: REVISION - - 4TH
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT;T05CM04911
44 E BROADWAY
LOFTS AND RETAIL

PROVIDE INFORMATION ON THE FOLLOWING,
1.THE ONE LINE LINE DRAWINGS FOR THE NEW PLANS (4TH REVISION) ARE QUITE DIFFERENT THAN THE DRAWINGS BROUGHT IN FOR REVIEW AS TO EXISTING CONDITIONS. SHEET E-2 NEW PLANS COMPARED TO OLD SHEET E4.1.

CONTACTED LONNIE RUSSEL TO COME IN TO DISCUSS DIFFERENCT ON TUESDAY 9/16/08, FROM 9---11AM. NO SHOW, AND NO ANSWER ON PHONE. PLANS DENID AND PUT BACK INTO PLAN CHECK UNTILLED NOTIFIED.

RAY T MAJUTA
DSD ELEXCTRICAL PLAN CK
CITY OF TUCSON
520-8374988
9/16/08

Final Status

Task End Date Reviewer's Name Type of Review Description
09/16/2008 SUE REEVES REJECT SHELF RECEIVED