Permit Number: T05CM04911
Parcel: 11713038C

Address:
44 E BROADWAY BL

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T05CM04911
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.
INCLUDE EMAIL ADDRESS OF ENGINEER/ARCHITECT/DESIGNER WITH NEXT SUBMITTAL
PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Demonstrate compliance with the Tucson Lighting Code. Starting point shall be Outdoor Lighting Ordinance Calculation, Sheet E1.1 of approved plans.
2. Submit cut sheets of all new exterior lighting.
3. Provide Mechanical Plans for new A/C, EFs, and Air Handler.
4. Provide Plumbing Plans for new W/H.
5. Load Summary not Code-compliant. Please resubmit load calculations with respect to those on the approved plans, Sheet E4.1. For example, the original Engineer of Record allotted 41.7A to Panel R1, and the actual load is 82.2A. This would bring the total amps to 1579A instead of 1538A. Still within the 1600A rating of the service.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
05/12/2008 SHANAE POWELL REJECT SHELF Completed