Permit Number: T05CM04911
Parcel: 11713038C

Address:
44 E BROADWAY BL

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T05CM04911
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2008 JWILLIA5 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/06/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the outside air is to be supplied to AC-1-1 and the quantity of outside air.
2. Indicate the relocation of AC-1-2.
3. Clearly indicate the relationship of the modified plumbing system to the approved drawings.