Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM04911
Parcel: 11713038C

Address:
44 E BROADWAY BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04911
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 5/03/06
ACTIVITY NUMBER: T05CM04911
PROJECT NAME: OFFICE BUILDING CONVERTED TO APTS & RETAIL
PROJECT ADDRESS: 44 E. BROADWAY
ARCHITECT / ENGINEER: PAUL WEINER
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.
1) Clarify / justify corridor space outside of dwelling unit 3 and dwelling unit 5 per section 1016.3. A dead end results whether or not egress elements open into it. This design is not code compliant. The building official is willing to consider the dead end corridor if the gate is shifted to 24ft down corridor and efforts are made to not appear that this is a exit. Appeal should be filed.
Waiting for smoke flow simulation to justify that ventilation is adequate. Provide approved appeal 06-04-01 or comply with code.

2) Clarify / justify atrium space per section 404. Provide smoke flow simulation if no exhaust system is going to be provided. Waiting for smoke flow simulation to justify that ventilation is adequate.
05/03/2006 AKLAPPE1 ZONING REVIEW Needs Review