Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM04911
Parcel: 11713038C

Address:
44 E BROADWAY BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04911
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/07/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/07/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/07/2006 GERRY KOZIOL WWM REVIEW Approved
04/18/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 4/18/06
ACTIVITY NUMBER: T05CM04911
PROJECT NAME: OFFICE BUILDING CONVERTED TO APTS & RETAIL
PROJECT ADDRESS: 44 E. BROADWAY
ARCHITECT / ENGINEER: PAUL WEINER
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1) Site plan must be approved before a building permit can be issued. It appears accessibility ramp needs to be revised per the ANSI A117.1 2003 at Jackson St. A 48"x30" flat area between trash enclosure drive apron and ramp needs to be provided.

2) Accessible means of egress are required see section 3406 change of occupancy requires the building to be fully accessible. See section 3409.3.
Please revise notes on drawings to clarify this is a wheel chair lift.

3) Clarify / justify corridor space outside of dwelling unit 3 and dwelling unit 5 per section 1016.3. A dead end results whether or not egress elements open into it. This design is not code compliant. The building official is willing to consider the dead end corridor if the gate is shifted to 24ft down corridor and efforts are made to not appear that this is a exit. Appeal should be filed.
Waiting for smoke flow simulation to justify that ventilation is adequate.

4) Clarify / justify atrium space per section 404. Provide smoke flow simulation if no exhaust system is going to be provided.

5) Provide structural calculations and detailing to justify/clarify the ceiling mount of electrical transformers.
04/18/2006 DAVID RIVERA ZONING REVIEW Denied Zoning cannot approve the building plans until the site plan has been approved and the building plans have been approved by the building reviewer.
04/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/18/2006 DAVID RIVERA ZONING REVIEW Completed Zoning cannot approve the building plans until the site plan has been approved and the building plans have been approved by the building reviewer.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed
04/19/2006 SUE REEVES REJECT SHELF Completed