Permit Number: T05CM04870
Parcel: 13314459C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04870
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2005 JIM EGAN FIRE REVIEW Approved
09/22/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/22/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE NUMERIC BREAKDOWN FOR 20% COST OF CONSTRUCTION SPENT TOWARDS MEETING ACCESSIBILITY REQUIREMENTS, sINCE RESTROOM IS NOT FULLY ACCESSIBLE.
2) WETBAR HEIGHT NEEDS TO BE PER ANSI A117.1 2003.
3) DID YOU WANT TO SPECIFY DETAIL 3/A-3 ON ELEVATION 10/A3.
4) CLARIFY INSTALLATION OF PARTITION DETAIL 20/A4. FURTHER DETAIL REQUIRED.
09/22/2005 ROBERT SHERRY WATER REVIEW Approved
09/22/2005 HEATHER THRALL ZONING REVIEW Approved
09/22/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the total airflow from the existing A/C units so that the 15% OSA can be evaluated for required ventilation.
2. Indicate the minimum insulation R-value for the duct insulation.
09/22/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04870 9/22/05

1. Specify how the grounding is to be accomplished for the telephone system. Reference NEC 800.40.
2. Indicate the exact location of New Panel S.
3. Keynote 8 on Single Line Riser, which calls for a #6 GND, is undersized for this application. Per Table 250.122, the minimum size shall be #3 due to the 400A rating of the OCPD Keynote 5.
4. Demonstrate that the Gutter Keynote 7 and its feeder Keynote 6 are not overloaded.
5. Provide fault calculations for New Panel S.
6. There are certain existing loads to be terminated to New Panel S. It is not clear which loads the Contractor is to terminate and Inspector is to check.
09/22/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/28/2005 JMORALE1 WWM REVIEW Needs Review