Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM04826
Parcel: 13502134B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04826
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2005 JIM EGAN FIRE REVIEW Approved
09/21/2005 DAVE MANN PLUMBING-COMMERCIAL REVIEW Approved
09/21/2005 HEATHER THRALL ZONING REVIEW Approved
09/21/2005 DAVE MANN MECHANICAL-COMMERCIAL REVIEW Approved
09/22/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM04826 9/21/05

1. Please refer to Sheet P2.0 for power requirements for Water Heater and Recirculation Pump. They do not appear on the panel schedule, and need a disconnect switch and panel and circuit # indicated on the power plan. Also needing correction is the proper specification of Water Heater power requirements: "4500/4500 Volts" is not reasonable; if Wattage is intended, note that (240) (10.4) = 2500W, not 4500. Coordinate with Plumbing and clarify.

2. Add load information on Panel Schedule for Ckt PF-26.
10/14/2005 GERRY KOZIOL WWM REVIEW Approved
10/14/2005 LOREN MAKUS ENGINEERING REVIEW Approved
10/14/2005 WATER WATER REVIEW Approved
10/14/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved S1. PROVIDE DESIGN PER 2003 IBC.
S2. PROVIDE COMPLETED CODE REVIEW CHECKLIST.
s3. PROVIDE CORRECT ADDRESS.