Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04826
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 09/21/2005 | DAVE MANN | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/21/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 09/21/2005 | DAVE MANN | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/22/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM04826 9/21/05 1. Please refer to Sheet P2.0 for power requirements for Water Heater and Recirculation Pump. They do not appear on the panel schedule, and need a disconnect switch and panel and circuit # indicated on the power plan. Also needing correction is the proper specification of Water Heater power requirements: "4500/4500 Volts" is not reasonable; if Wattage is intended, note that (240) (10.4) = 2500W, not 4500. Coordinate with Plumbing and clarify. 2. Add load information on Panel Schedule for Ckt PF-26. |
| 10/14/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/14/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/14/2005 | WATER | WATER | REVIEW | Approved | |
| 10/14/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | S1. PROVIDE DESIGN PER 2003 IBC. S2. PROVIDE COMPLETED CODE REVIEW CHECKLIST. s3. PROVIDE CORRECT ADDRESS. |