Permit Number: T05CM04826
Parcel: 13502134B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04826
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the waste for the sanitizing section of the 3-compartment sink to drain indirectly to the floor sink. If the indirect wate pipe is 15 feet over longer, it must be independently vented. Reference Section 803.0, UPC 1994.
2. Show that the listing of the T&P valve is not violated by the proposed installation.