Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM04826
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the waste for the sanitizing section of the 3-compartment sink to drain indirectly to the floor sink. If the indirect wate pipe is 15 feet over longer, it must be independently vented. Reference Section 803.0, UPC 1994. 2. Show that the listing of the T&P valve is not violated by the proposed installation. |