Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2005 JIM EGAN FIRE REVIEW Approved
10/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/05/2005 ROBERT SHERRY WATER REVIEW Approved
10/14/2005 SREEVES1 WWM REVIEW Passed no plbg
10/19/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Minimum font size is 10 point, just a bit over 1/8".
2. Fill in load on panel schedule Ckt 11 for track lighting.
3. General Note #1, Sheet E-1, specify NEC 2002.
4. Multiply all continuous loads by 25% for feeder and service load calculations.
5. Provide for the transformer grounding as a Derived System per NEC 250.30.
6. Provide for overcurrent protection for the New Transformer, and its feeder. Reference NEC 450.3.
7. Consider power factor in service load calculation, as appropriate.
11/01/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
11/14/2005 SUE REEVES REJECT SHELF Completed