Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04803
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/05/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/14/2005 | SREEVES1 | WWM | REVIEW | Passed | no plbg |
| 10/19/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Minimum font size is 10 point, just a bit over 1/8". 2. Fill in load on panel schedule Ckt 11 for track lighting. 3. General Note #1, Sheet E-1, specify NEC 2002. 4. Multiply all continuous loads by 25% for feeder and service load calculations. 5. Provide for the transformer grounding as a Derived System per NEC 250.30. 6. Provide for overcurrent protection for the New Transformer, and its feeder. Reference NEC 450.3. 7. Consider power factor in service load calculation, as appropriate. |
| 11/01/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/14/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 11/14/2005 | SUE REEVES | REJECT SHELF | Completed |