Permit Number: T05CM04793
Parcel: 13613001R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04793
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2005 JIM EGAN FIRE REVIEW Approved
10/12/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the removal of one urinal does not result in too few fixtures.
2. The minimum font size is 10 points.
10/12/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04793 10/12/05

1. Minimum font size 10 point, which is a bit over 1/8".
2. Provide a lighting fixture schedule for the new fixtures.
3. Fault calculations available at Panels LP and AP3 are shown as 24219, but the panels are rated for 10K. Please clarify, and note that if the panels are existing, under a previously approved permit, it is not necessary to submit fault calculations unless there is an unsafe condition which must be corrected.
10/12/2005 ROBERT SHERRY WATER REVIEW Approved
10/12/2005 HEATHER THRALL ZONING REVIEW Approved
10/12/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/12/2005 LOREN MAKUS ENGINEERING REVIEW Approved
10/26/2005 GERRY KOZIOL WWM REVIEW Approved
10/26/2005 KMEDINA1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2005 KMEDINA1 OUT TO CUSTOMER Completed