Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04793
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/12/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
10/12/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the removal of one urinal does not result in too few fixtures. 2. The minimum font size is 10 points. |
10/12/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM04793 10/12/05 1. Minimum font size 10 point, which is a bit over 1/8". 2. Provide a lighting fixture schedule for the new fixtures. 3. Fault calculations available at Panels LP and AP3 are shown as 24219, but the panels are rated for 10K. Please clarify, and note that if the panels are existing, under a previously approved permit, it is not necessary to submit fault calculations unless there is an unsafe condition which must be corrected. |
10/12/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/12/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
10/12/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/12/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
10/26/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/26/2005 | KMEDINA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/26/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |