Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM04774
Parcel: 11007414F

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM04774
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The water calculation references Section 610.4, UPC 1994 but the calculation is not complete and does not conform to the requirements of Sections 610.7, 610.9, and 610.10. (Provide the total length of the piping system from the meter to the most remote outlet.)
2. Relocate the access panel for the water heater to provide access to the water heater.
10/03/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved