Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T05CM04774
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The water calculation references Section 610.4, UPC 1994 but the calculation is not complete and does not conform to the requirements of Sections 610.7, 610.9, and 610.10. (Provide the total length of the piping system from the meter to the most remote outlet.) 2. Relocate the access panel for the water heater to provide access to the water heater. |
| 10/03/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved |