Permit Number: T05CM04758
Parcel: 11006159B

Review Status: Active

Review Details: REVISION - - 3RD

Permit Number - T05CM04758
Review Name: REVISION - - 3RD
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM04758 8/22/07

1. Unit numbers on the service disconnecting means do not correspond to those on approved drawings.
2. Provide size of disconnecting means.
3. Provide size of Grounding Electrode Conductor.