Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM04757
Parcel: 11006159B

Review Status: Active

Review Details: REVISION - - 2ND

Permit Number - T05CM04757
Review Name: REVISION - - 2ND
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM04757 8/22/07

1. Unit numbers on the service disconnecting means do not correspond to those on approved drawings.
2. Provide size of disconnecting means.
3. Provide size of Grounding Electrode Conductor.