Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04747
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/16/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
09/29/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2000. 2. Condensate drains may not terminate over a roof drain unless the roof drain terminates at or above grade in an area capable or absorbing the condensate flow without surface drainage. Reference Section 307.2.1, IMC 2000, as amended by the City of Tucson. |
09/29/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide the connection of the TV to it's support. Specify the sizes and number of connectors, also the size of the supporting elements. 2) Some notes on the SP sheets make reference to city of Mesa. Change these notes referene City of Tucson. 3) NOTE ON PLANS, ALL EXTERIOR SIGNS SHALL BE UNDER SEPARARE PERMIT. |
09/29/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/30/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Confirm that suspended water heater complies with the access requirements of section 511.0, UPC 1994 with AZ State amendments. 2. Termination of the excess pressure relief from the water heater into an overhead overflow pan is not approved location. Reference Section 608.5, UPC 1994. 3. Clarify what a "funnel receptor at lavatory trap tailpiece" consists of and how it complies with Sections 804.1 and 1001.2, UPC 1994. 4. Clarify the meaning of the keynotes (?) on the toilet room plumbing plan. Reference Section 103.2.3, UPC 1994. 5. Revise the toilet room plumbing plan to show the hot water connected to the left side of the lavatory. Reference Section 601.2, UPC 1994. 6. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference Section 804.3, IECC 2000. 7. Clarify which type of trap primer valve is to be installed (Josam 88250 or PPP PR-500), its location and how it is to be accessed. Reference Section 103.2.3, UPC 1994. 8. Revise the notes to reference the applicable codes; the 1997 Florida Accessibility Code is not recognized in this jurisdiction. 9. Provide water pressure and water pipe sizing calculations. Reference Appendix A, UPC 1994. 10. If the water hammer arrester specified in the plumbing fixture schedule is to be installed, show its location on the drawing. Reference Section 103.2.3, UPC 1994. |
10/12/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/18/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Circuit L-25 has been used twice, once for the sign, and once for the RTU outlet. 2. Please include a load of 200 VA /LF for the Show Windows on Ckt L-1. Reference NEC 220.12 (A). 3. With 400W MH lighting per the Light Fixture Schedule, Ckts L-2, L-4, and L-6 should be counted as 1200, 1600, and 1600 VA respectively. Verify that all lighting and sign electrical loads are counted at 1.25% in the Load Summary. 4. Carrier does not provide 20 KW heat on the RTU specified, according to the Mechanical Plans Examiner. MCA is 59A according to the catalogue cut sheet, which would compute to about 49.0 KVA, not 20. A quick check of load calculations, given this comment and those above, results in an electrical load of about 103A, which would overload the panel and conductor specified for this installation. 5. It appears that the load on Panel L is 36.4 KVA, which may overload the 30 KVA X'FMR. This considers the sign, track lighting, and other lighting at 1.25%. This may also overload the #8 conductor. 6. Provide load calculations to demonstrate that service and any distribution panels are not overloaded. 7. Electrical Specifications Fire Alarm System Notes are not necessary, because the requirement for a duct detector is satisfied on the same page, and such notes are furthermore incorrect because they imply that the Contractor may design such a system, which would not be permitted in this jurisdiction. Note that Fire has approved this set for construction. 8. Electrical Specifications Method and Materials Note 17 refers to NEC 250-72. No such section on the 2002 NEC. |