Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM04747
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/08/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | 1. If the specified point-of-use water heater has a storage volume with an inside diameter of 3" or greater, provide an approved combination pressure and temperature relief valve. Reference Section 608.3, UPC 1994. 2. Clarify the meaning of the keynotes (?) on the toilet room plumbing plan. Is "A" a water closet of a water heater? Reference Section 103.2.3, UPC 1994. |
11/08/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | 1. Show the route and termination of the condensate drains on the plans. If the condensate drain is to terminate over a roof drain, verify that it does not terminate at or above grade in an area incapable of absorbing the condensate flow without surface drainage. Reference Section 307.2.1, IMC 2000, as amended by the City of Tucson. |
11/22/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/22/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Calculation using peak demand is specified in NEC 220.35. See the following, assuming pf of 0.85. (2230/0.85 X 1.25) + 108 = 3387. This exceeds the 3000A bussing capacity. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/25/2005 | SUE REEVES | OUT TO CUSTOMER | Completed |