Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM04747
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04747
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved 1. If the specified point-of-use water heater has a storage volume with an inside diameter of 3" or greater, provide an approved combination pressure and temperature relief valve. Reference Section 608.3, UPC 1994.
2. Clarify the meaning of the keynotes (?) on the toilet room plumbing plan. Is "A" a water closet of a water heater? Reference Section 103.2.3, UPC 1994.
11/08/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved 1. Show the route and termination of the condensate drains on the plans. If the condensate drain is to terminate over a roof drain, verify that it does not terminate at or above grade in an area incapable of absorbing the condensate flow without surface drainage. Reference Section 307.2.1, IMC 2000, as amended by the City of Tucson.
11/22/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
11/22/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Calculation using peak demand is specified in NEC 220.35. See the following, assuming pf of 0.85. (2230/0.85 X 1.25) + 108 = 3387. This exceeds the 3000A bussing capacity.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/25/2005 SUE REEVES OUT TO CUSTOMER Completed