Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM04744
Parcel: 113061320

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04744
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM04744 12/16/05 REVIEW OF 30 KW GENERATOR

1. Minimum font size is 10 point, which is a little over 1/8". New Panel Schedule too small.
2. Fault calculations use 208V. system is 240V.
3. Fault calculations use "c" value of 13923. That value for 4/0 non-metallic is 16673.
4. Disconnect appears to be rated at too low a fault current value.
5. There are two Revision 2s indicated, of different dates. Please clarify.
6. Only need to submit revised sheets. If the entire set is re-submitted, then each Reviewer will need to be consulted once again.
11/30/2005 DAN CASTRO ZONING REVIEW Denied 1. Provide documentation required by special exception condition number two (2).

2. Per Dave Koss, Real Estate Division of the Transportation Department, we do not have an approved lease agreement for this project. The agreement is to allow for the proposed antenna on a TEP power pole located within public right-of-way. Contact Mr. Koss at 791-4181 for information regarding the lease agreement required. A copy of the lease agreement must be provided to the Zoning Review section prior to site plan approval.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180. An appointment is required to discuss these comments in person.
11/30/2005 ANDREW CONNOR LANDSCAPE REVIEW Passed
12/16/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved