Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM04737
Parcel: 11307086A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04737
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2005 LOREN MAKUS ENGINEERING REVIEW Approved
09/15/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the three shampoo sinks are to be installed.
2. Provide upper terminal cleanouts at the clotheswasher and the water closet.
09/15/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
09/15/2005 ROBERT SHERRY WATER REVIEW Approved
09/15/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04737 9/15/05

1. Ckt A-12 has been used twice, once on the Lighting Plan, and again on the Power Plan for the EF.
2. A-15 load on panel schedule does not correspond with load on Power Plan.
3. A-17 load on panel schedule does not correspond with load on Power Plan.
4. It is unclear why Ckt A-15,17 needs to be 15A/2-pole.
5. Panel schedule indicates 100A, which would be overloaded. Please clarify.
6. WH is 15 KW on Plumbing. Please coordinate with Mechanical.
09/15/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/21/2005 CAGUILA1 ZONING REVIEW Needs Review
09/21/2005 CAGUILA1 WWM REVIEW Needs Review
09/21/2005 JIM EGAN FIRE REVIEW Approved