Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04737
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/15/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/15/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the three shampoo sinks are to be installed. 2. Provide upper terminal cleanouts at the clotheswasher and the water closet. |
| 09/15/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/15/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/15/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/15/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM04737 9/15/05 1. Ckt A-12 has been used twice, once on the Lighting Plan, and again on the Power Plan for the EF. 2. A-15 load on panel schedule does not correspond with load on Power Plan. 3. A-17 load on panel schedule does not correspond with load on Power Plan. 4. It is unclear why Ckt A-15,17 needs to be 15A/2-pole. 5. Panel schedule indicates 100A, which would be overloaded. Please clarify. 6. WH is 15 KW on Plumbing. Please coordinate with Mechanical. |
| 09/21/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 09/21/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 09/21/2005 | JIM EGAN | FIRE | REVIEW | Approved |