Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T05CM04733
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2000. 2. The minimum insulation for ducts (including flex ducts) located in unconditioned spaces within the building envelope is R-5. Reference Section 803.2.8, IECC 2000. 3. Terminate condensate drains in accordance with Section 307.2.1, IMC 2000, as amended by the City of Tucson (i.e. not to the tailpiece of a sink). 4. Clarify the spacing of the pipe supports and verify that it complies with either Section 305.4, IMC 2000 or MSS SP-69. |
09/28/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The submitted water pressure calculations do not support the size of water piping to the fixtures. Reference Section 610.1, UPC 1994. 2. Provide roof drainage calculations to justify the size of the scuppers. Reference Appendix D, UPC 1994. 3. Increase the size of the overflow in the roof drain collector box to equal the size of the scupper. Reference Section D1.1 (d), UPC 1994. |
10/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/12/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | WASTEWATER- NEEDS TO WORK WITH DICKIE FERNANDEZ @740-6947- DSC/WASTEWATER 2ND FLOOR. PUBLIC SEWER G-01-153 HAS NOT BEEN ACCEPTED & HAS NOT BEEN RELEASED BY PCWWM |
10/20/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Specify the number of water fixtures and lavatories re- quired and the number provided. 2) Note and show on details that allowable soil pressure is 1500 psf. at 18" below undisturbed soil. 3) Provide engineering calcs for ramada. |
10/24/2005 | DAN CASTRO | ZONING | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/28/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
11/28/2005 | SUE REEVES | REJECT SHELF | Completed |