Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM04733
Parcel: 119280310

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM04733
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2000.
2. The minimum insulation for ducts (including flex ducts) located in unconditioned spaces within the building envelope is R-5. Reference Section 803.2.8, IECC 2000.
3. Terminate condensate drains in accordance with Section 307.2.1, IMC 2000, as amended by the City of Tucson (i.e. not to the tailpiece of a sink).
4. Clarify the spacing of the pipe supports and verify that it complies with either Section 305.4, IMC 2000 or MSS SP-69.
09/28/2005 ROBERT SHERRY WATER REVIEW Approved
09/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The submitted water pressure calculations do not support the size of water piping to the fixtures. Reference Section 610.1, UPC 1994.
2. Provide roof drainage calculations to justify the size of the scuppers. Reference Appendix D, UPC 1994.
3. Increase the size of the overflow in the roof drain collector box to equal the size of the scupper. Reference Section D1.1 (d), UPC 1994.
10/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/12/2005 GERRY KOZIOL WWM REVIEW Denied WASTEWATER- NEEDS TO WORK WITH DICKIE FERNANDEZ @740-6947- DSC/WASTEWATER 2ND FLOOR. PUBLIC SEWER G-01-153 HAS NOT BEEN ACCEPTED & HAS NOT BEEN RELEASED BY PCWWM
10/20/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Specify the number of water fixtures and lavatories re-
quired and the number provided.
2) Note and show on details that allowable soil pressure is
1500 psf. at 18" below undisturbed soil.
3) Provide engineering calcs for ramada.
10/24/2005 DAN CASTRO ZONING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/28/2005 JMORALE1 OUT TO CUSTOMER Completed
11/28/2005 SUE REEVES REJECT SHELF Completed