Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Permit Number - T05CM04729
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/10/2005 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 11/01/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | CDRC TRANSMITTAL FROM: Michael St.Paul FOR: David Rivera Planner Technician Principal Planner PROJECT: T05CM04729 8821 East Appomattox Street Second unit in R-1 zone TRANSMITTAL: COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. CODE SECTION/ DEVELOPMENT STANDARD 1. This review is for a second unit in the R-1 zone. The Development Designator is "H" and the subject to is Section 3.5.7.1. The minimum lot size is 10,000 square feet. The maximum lot coverage is 70%. The Perimeter Yard Indicator is AA. LUC Sec 2.3.4.2.A.2 & LUC Sec 3.2.3.1.B 2. Please provide the last approved site plan. The site plan depicts a carport in the front yard and a garage in the rear yard. It appears that each would have required permits. The site plan submitted depicts a carport in the front yard that may or may not be attached. The elevation plans depict the carport as detached. The site plan appears to show the carport as attached. In either case a Board of Adjustment variance or a Design Development Option would have been required. In addition, the minimum setback required is the greater of 20'-0" or one and one half the height of the structure's wall facing the front property line. LUC Sec 3.2.5.3.C LUC Sec 3.2.6.5.A LUC Sec 3.2.6.5.B.2.a 3. Please clarify the heights of the structural walls on the elevations and the site plan. Provide the measurements from design grade (ground level for the foundation) and the highest point of the walls. This information is required to determine the side and front setback requirements for this plan. LUC Sec 3.2.6.3 LUC Sec 3.2.6.4 LUC Sec 3.2.6.5 4. Please identify all existing and proposed structures on the site plan. There appears to be a structure to the north side of the pool that has setback dimensions but it is not labeled. 5. Please provide dimensions for the placement of the existing and proposed structures along the front property line. LUC Sec 3.2.6.5.A 6. With the second dwelling having two bedrooms a minimum of three parking spaces are required. "All the parking and maneuvering must be located on site, either in the side or rear perimeter yard. The vehicular use area must be improved, with includes surfacing, striping, and provision of barriers, in conformance with Development Standard 3-05.3.0. Parking spaces may not be located in a vehicular use area in any front street perimeter yard." LUC Sec 3.5.7.1.H 7. The floor plan on the site plan does not match the floor plan. Please revise the site plan to match the floor plan. |
| 11/02/2005 | NEAL SAUNDERS | BUILDING-RESIDENTIAL | REVIEW | Denied | Plan Check Comments - Project T05cm04729 Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. General Requirements 1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned. 2. Pen and Pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes. Floor Plan 1. Provide tempered glass in all windows that meet requirements of R308.4. 2. Note and specify that shower enclosures shall have a minimum finished interior area of 1,024 square inches and shall be capable of encompassing a minimum 30" circle per 1994 UPC SEC. 410.0. All glass enclosures shall be tempered. 3. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front not less than 21" per figure R307.2. Structural Plan 1. S1- Detail 10/S-3 is called out at the south wall footing. Should this be 1/S-3? 2. Detail 5/S-3 at bench and screenwall is unclear as to the construction. Note says "..bottom of window..". Also width of wall is far less than the floor plan suggests for the screenwall. Clarify. 3. Specify width of all foundations - Foundation schedule is not referenced from anywhere. Details 2, 4, 5, and 7 are all missing footing sizes. 4. Note on the drawings the allowable soil bearing pressure used in the design of the footings, or state that the assumed value of 1500 PSF is being used per table R401.4.1. 5. Callout all lintels over all openings. 6. Masonry lintels require engineered design. Provide or remove schedule. 7. Specify joists where they occur on roof framing plan. 8. Details 1/S-4 and 2/S-4 - Size ledgers and anchor bolts (size and spacing). 9. Callout beams on framing plan as suggested by detail 9/S-4. 10. Specify slope of all roofs. 11. Provide cross-section and/or details for CMU wall support above large window units in kitchen and living room. How are the assemblies constructed? 12. Locate details 5/S-4, 6/S-4 and 10/S-4. 13. 11/S-5 - Provide size of footer. 14. Show compliance with 1001.15 - Chimney clearances. 15. Provide cross-section of arch construction. 16. Locate details 1/S-5, 3/S-5 and 4/S-5. 17. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply. Plumbing Plan 1. Note that bathtub and shower enclosures shall be finished per P2710 with ceramic tile, or a listed enclosure, to a height of 72" above the drain per R702.4 and R307.2. 2. Water line: Provide the total fixture unit demand and maximum developed length. Include size of supply line from meter to house. Revise per Tables 6.3 and 6.4, 1994 UPC. 3. Provide and show pressure and temperature relief valve at water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down. 4. The City of Tucson has adopted the 1994 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). All plans must reference this code. Revise all notes 5. Size all waste (traps and vents) and water lines on plan. 6. Water line discrepancy on page p-1 and site plan - 1-1/2" vs. 1". Mechanical Plan 1. Note on plans: Mechanical shall comply with 2003 IRC chapters 13 - 24. 2. Return air DUCT shall be sized per IRC sections M1602.2. (gas furnace - 2 sq. in. / 1000 BTU; heat pump / air conditioner - 6 sq. in. / 1000 BTU) (1ton cooling = 12,000 BTU) Electrical Plans 1. Note on plans: Electrical work shall comply wit chapters 33-42 2003 IRC. 2. Note the location, type and amperage of the panel. Note the grounding and bonding method. Metallic gas lines must be bonded and shall not be used as grounding method. 3. Designate the location and circuit of all required light fixtures, receptacles, and switches. Provide a panel schedule noting circuit number and size along with a general description. 4. At least one wall switch controlled light must be provided at outdoor entrances or exits per E3803.3. 5. Provide an exterior outlet at grade level located at both the front and back of the dwelling, per E3801.7. these outlets shall be GFCI protected per E3802.3. 6. Receptacle outlets shall be provided at each kitchen counter space wider than 12", and shall be installed so that no point along the wall line is more than 24" from a receptacle outlet, per E3801.4.1. 7. Island or peninsula counter tops shall have at least one receptacle outlet at each counter space with a long dimension of 24" or greater, and a short dimension of 12" or greater, per E3801.4.2 and E3801.4.3. 8. A receptacle outlet shall be provided adjacent to the basin in each bathroom, per E3801.6. Bathroom outlets shall be on a separate 20 AMP circuit with no other outlets, per E3603.4. 9. All receptacle outlets in bathrooms, kitchens, unfinished basements, garages or carports, at grade level and within 6' of a wet bar or kitchen sink shall have ground fault circuit interrupting protection. Note on the drawings at each outlet requiring such protection, per E3802. 10. Note that two or more 2O AMP small appliance circuits shall be provided to serve all receptacles outlets in the kitchen, breakfast room and dining room. Such circuits shall have no other outlets, per E3603.2 and E3801.3 through E3801.4.5. Both circuits must be present at the countertops. 11. Note that at least one 20 AMP branch circuit shall be installed to serve the laundry room and this circuit shall have no other outlets, per E3603.3 and 3801.8. 12. Indicate the location of all air conditioning and heating units, air handlers, compressors, and disconnects. 13. Electrical load calculations are required when more than 4 circuits are added. 14. Submit panel schedule showing circuit ampacity, wire size, panel size and circuit numbers. 15. Provide arc-fault protection for all outlets in bedrooms per E3802.11. 16. Show locations of smoke detectors per R313. Outdoor Lighting Code 1. Show compliance with City of Tucson Outdoor Lighting Code (www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf). 2. Provide cut sheets of chosen lights. If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113. NOTE: As of 09/06/04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code. All model plans shall reference these codes. 9. |
| 11/08/2005 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: C.G. Urias DATE: November 14, 2005 Architect 6136 E. West Miramar Drive Tucson, Arizona 85715 SUBJECT: Garigan Residence, 8821 E Appomattox St. Site/Bldg. plan T05CM04729 (First Review) T14S, R15E, Section 05 RESUBMITTAL REQUIRED: Site/Bldg. Plan and Drainage Report. The Development Plan (DP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Site/Bldg. Plan: 1. Please include a response letter to the comments along with the corrected copies of the DP. 2. The FUP cannot be approved prior to the site/bldg. plan. 3. The FFE recommended in the DR does not match the FFE on the constructions plans. Use the elevation recommended in the DR and list the datum. 4. Show the 100-year flood plain limits and EHS on the construction plans. 5. Show the appropriate openings in the block patio wall to allow the 100-year event to flow through. 6. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16. 7. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. 8. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. It appears the building's FFE is excessively high, justification will be required to maintain that elevation. Show existing and proposed grades along the east property line. 9. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. Drainage Report: 1. Please include a response letter to the comments along with the corrected copies of the DR. 2. List the datum used in the DR. The FFE recommended in the DR does not match the FFE on the constructions plans. It may be the same elevation using two different datums, however a conversion equation must be shown. 3. Show the 100-year flood plain limits and EHS on the exhibit and on the construction plans. 4. Show the appropriate openings in the block patio wall to allow the 100-year event to flow through. If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1193 office (520) 879-8010 fax C:/8821 E Appomattox St Site-Bldg |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/15/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 11/15/2005 | SUE REEVES | REJECT SHELF | Completed |