Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T05CM04699
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2005 | JIM EGAN | FIRE | REVIEW | Denied | Fire sprinklers required per 2003 IBC Sec. 903.2.7 |
| 09/26/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/27/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The total flow for the private sewage collection system for this project is in excess of 3000 gallons per day. The design for the system must be submitted to the Pima County Department of Environmental Quality for their approval prior to obtaining a permit for constructing the sewage collection system from the City of Tucson. Reference A. R. S. 49-104 (B) (13). 2. Provide the Civil drawings referenced on sheet P1.1 that show the water supply piping to the new apartments. Reference Section 103.2.3, UPC 1994. 3. The trap and trap arm for a lavatory may not be increased more than one size larger than the minimum trap size shown in Table 7-3. Reference Section 1003.3, UPC 1994. 4. Clarify the routing and connections (non-mirrored) to the building drain as shown in detail 2/P1.1. Reference Section 103.2.3, UPC 1994. 5. Provide the listing for the two-way cleanout fitting called out in detail 2/P1.1. Reference Section 103.2.3, UPC 1994. 6. Coordinate the plumbing layout with the architectural background - the water closet is not normally located in the bathtub. |
| 09/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the duct and HVAC equipment layout with the architectural background. 2. Remove the dryer exhaust ducts from the 1-hour fire partition between the apartments or provide a listed wall construction detail that will accommodate the ducts. 3. Provide information to show that the proposed size of the dryer exhaust duct is approved for use by the dryer manufacturer. Reference Section 504.6, IMC 2000. 4. Provide information to show that the closet installation of the clothes dryer conforms to Section 504.5, IMC 2000. 5. Clarify the route of the exhaust duct for the range hood. Reference Section 106.3.1, IMC 2000. |
| 10/11/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/12/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/18/2005 | DAN CASTRO | ZONING | REVIEW | Denied | 1. A copy of the stamped approved site plan, landscape plan, and NPPO plan shall be inserted into each building plan set. One stamped approve set was submitted for this building plan review. 2. Proposed building 3 on the site plan shows a breezeway and the floor plan on sheet A1.1 does not. Revise one or the other for consistency. 3. Building heights provided on the elevation drawings are higher than the building heights proposed on the site plan. For example, on the approved site plan, building 3 is labeled as having a 13'6" height to the top of the structure. The east elevation on sheet A2.2 has a building height well over 14 feet from design grade measured to the top of the parapet wall. Re-check all building wall heights shown in the elevation drawings and provide dimensions from design grade to the highest point of the exterior building wall (top of parapet wall). If the proposed building heights require a greater building setback than what is shown on the approved site plan, a revised site plan will be required and Design Development Option approval will be required for the insufficient interior perimeter yard/s. |
| 10/20/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ON TO5CM04698 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/26/2005 | DELMA ROBEY | OUT TO CUSTOMER | Completed |