Permit Number: T05CM04699
Parcel: 106030150

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04699
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2006 JMORALE1 ZONING REVIEW Needs Review
12/21/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/21/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Plumbing drawings can be approved upon receipt of the construction authorization for the private sewage collection system by the Pima County Department of Environmental Quality. Reference A. R. S. 49-104 (B) (13).
12/21/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show that the closet installation of the clothes dryer conforms to Section 504.5, IMC 2000. (Refer to the manufacturer's installation instructions for the requirements for closet installations.)