Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2006 STANTEC 2ND PARTY REVIEW REVIEW Denied March 24, 2006


To: City of Tucson Development Services Department
201 N. Stone Avenue, First Floor
Tucson, Arizona 85701
Attn: David Mann, P.E., Building Code Division

Cc: Roy Noggle Associates, architects
1301 E. Maryland Ave.
Phoenix, AZ 8501
Attn: Roy Noggle

Re: Finch Residence – Additions, Carport and Workshop
City of Tucson No. T05CM04671
Stantec Project No. 816-30015-01 (080)




Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back-check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating the action taken.

SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical, Model Energy and Electrical codes. All code references are to the 2003 International Residential Code (IRC). All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

ARCHITECTURAL:

There are no comments to address.

STRUCTURAL:

There are no comments to address.

PLUMBING PLANS:

The plan fails to denote to depict the usage of drainage cleanouts for individual waste stacks. Provide missing requirements.

Provide proof that the existing invert of the sewer in the street is capable of handling the new sewer load connection without a sump pump connection.

Please provide notation on this set of drawings stipulating the new sewer run for the addition will meet [2003 UPC Sec’s 708.0 & 718.1] min. slope of ¼” per foot or slope certification shall be presented to the building inspector from a registered land surveyor before approval of the pipe laid.

The provided plumbing isometric sheet P 100 is devoid of any venting. Provide.

Provide a shut off valve at the waterline entrance into the workroom’s building perimeter.

MECHANICAL PLANS:

Denote methods to be compliant with 2003 IRC Sec R303.4.1 for the roof top unit and the plumbing vents.

Denote the route and termination to the outside for the restroom exhaust fan per 2003 IRC Sec. R303.5

ELECTRICAL PLANS:

The applicant is requested to provide an electric load calculation that is compliant with [2003 IRC Sec. E3502]. The service riser is the new 200-amp panel ‘WP’. Therefore, the load calculation is a depiction of the actual connected circuit loads in the 200-amp panel. Provide a feeder load calculation per [2003 IRC Table E3604.3 (1)&(2)] for the sub-panel ‘IP & HP’ as separate calculations to derive the breaker sizes for these two branch circuits inside the 200 amp panel ‘WP’.

Provide the location of sub-panel ‘IP & HP’.

When a major remodel such as this project is added, the entire site must be brought into lighting code compliance. Therefore a plan depicting all site light usage must be submitted. Outdoor Lighting Code 5.1.1, 5.1.2 & Section 4 of the code notes that fixture types installed under canopies, porches or roof areas must be full cut off fixture types themselves, not denoted as such by arbitrary placement. Photo(s) of existing use for proof of fixture(s) are accepted in lieu of manufacturer’s cut sheets. Provide calculation and fixtures.

MODEL ENERGY CODE:

Provide a proof of building envelope compliance.

-End of Review-

If you have any questions, please call (520) 750-7474.

Sincerely,
Stantec Consulting Inc.




Steven L. Nygren, R.A.
Senior Plans Examiner

SLN:sln

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed
04/04/2006 SUE REEVES REJECT SHELF Completed