Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Permit Number - T05CM04670
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2005 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 09/16/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 09/19/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | need 8th floor credit evaluation |
| 10/10/2005 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 10/17/2005 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS for Activity # T05CM04670 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. FLOOR PLANS: 1. Show that the remaining window of the south bedroom complies with R310 for providing emergency escape. 2. Note that tub/shower enclosures shall have nonabsorbent surfaces to 6' above the floor, R307.2. All glass enclosures shall be tempered, R308.4.5. STRUCTURAL PLANS: 1. For roofing option 38c specify roof system weight items (for example, weight of selected tile). Provide ICBO evaluation report number and manufacturer of all concrete or clay-type roofing, or note the requirement for deferred submittal to building inspector at installation. SECTIONS - DETAILS - MISC. NOTES: 1. Change the roof framing to wall detail (garage storage area) reference shown as detail 7/8 on the lower roof framing plan, sheet 6. 2. Note ceiling gypsum board shall be either 5/8" or ½" sag resistant when applied to 24" o/c framing, IRC table R702.3.5 footnote d. 3. Correct the conflict between the unvented attic note and the gable vents shown on the north and south elevations, sheet 3. 4. Show the calculation of area in compliance with R806.2 if attic ventilation is used. Note only 80% of the required ventilating area may be provided by ridge or gable vents when applying the reduced area calculation. Show the amount of eave vents needed to comply. 5. Show that the existing structure has sufficient attic venting if the new structure blocked any existing attic venting. PLUMBING PLANS: 1. The City of Tucson has adopted the 1994 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). All plans must reference this code. 2. Provide the total fixture unit demand for the entire property per 1994 UPC Table 6-3, and determine the supply line diameter from Table 6-4 assuming 46 to 60 psi. 3. Provide a pressure and temperature relief valve at the water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down, UPC 608.5. 4. Note and specify graywater waste line compliance with UPC Appendix G, State amendment. ELECTRICAL PLANS: 1. Designate the circuit number of all new light fixtures, receptacles, and switches, located in the existing structure, E3606.2. 2. A receptacle outlet shall be provided adjacent to the basin in each bathroom, E3801.6. Bathroom receptacles shall be on a separate 20 AMP circuit (A13) with no other outlets, E3603.4. 3. Lights installed over shower or bathtub must be approved for use in wet area, E3903.8. 4. All receptacle outlets in bathrooms, kitchens, and garages at grade level and within 6' of a wet bar or sink shall have ground fault circuit interrupting protection. Note on the drawings at each outlet requiring such protection, E3802. OUTDOOR LIGHTING CODE 1. Show compliance with City of Tucson Outdoor Lighting Code www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf 2. Provide cut sheets of selected light fixtures and lamp wattage before installation. MODEL ENERGY CODE: 1. Provide energy calculations per the 2000 IECC w/ local amendments (climate zone 4B, 2100 HDD) complying with 2003 IRC chapter 11 to support selected "R" values of insulation and "U" values of the windows and doors. http://www.energycodes.gov/rescheck/ If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/04/2006 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 01/04/2006 | JMORALE1 | REJECT SHELF | Completed |