Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T05CM04607
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/25/2005 | NEAL SAUNDERS | BUILDING-RESIDENTIAL | REVIEW | Denied | Plan Check Comments - Project T05cm04607 Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. General Requirements 1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned. 2. Pen or Pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes. Structural Plan 1. B/4 - Detail titled 'Exterior wall existing footing' yet there is no indication of any existing structure. Clarify. 2. Cross section notes existing roof over family room and master bedroom addition. In conjunction with detail B/4, can I assume that these additions are some sort of porch enclosure? Clarify and note on plans. Specify framing of existing roof. 3. Specify exterior finish on all pertinent details. 4. E/4 - Dimension 6" from post to grade. 5. F/4 - 1/2" diameter bolts are minimum size per R606.10(1). Specify construction of existing wall and specify type of bolt. 6. Specify roofing over new porch. 7. Detail bearing condition for porch roof over new family room exterior wall. Mechanical, Plumbing and Electrical Plan 1. Provide specifications of new mechanical unit. Is existing roof adequate to handle weight of this unit? 2. Provide total developed length of water line (meter to most remote fixture). Size supply line from meter to house. See table 6-4, 1994 UPC for adequate sizing. 3. Provide smoke detector in new mater bedroom and in vicinity of the room (i.e. hall/family room). 4. Justify 16 receptacles on circuit 30. 5. Provide arc-fault protection for all outlets in new mater bedroom. MODEL ENERGY CODE: 1. NOTE: If addition is < 20% of total square footage of dwelling, you are not required to meet MEC requirements. 1. Provide energy calculations per the 2000 IECC and comply with IRC chapter 11 or 'Rescheck' (www.energycodes.gov/rescheck/). 2. Call out on the plan the "R" values of insulation, as well as the "U" values of the windows and doors in compliance with the energy calculations provided. Windows must be low 'E'. If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/28/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |