Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2005 JIM EGAN FIRE REVIEW Approved
09/06/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the fixture identification numbers with the drawings. (e.g. P-13 or P-7. P-5 and P-6)
2. Show the size of the trap arm for P-7 (P-13).
3. Show the size of the runout for P-3. 3/4" copper is too small for a urinal.
4. Revise the flowrate demand as noted in the water calculation to comply with Section 610.1, UPC 1994.
09/06/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY LOCATION OF THE FOLLOWING DETAILS SK1/A1.0, 13/A2.0, 14/A2.0.
2) CLARIFY ELEVATIONS FOR OFFICES WITH WINDOWS.
3) CLARIFY ROOF FRAMIMG WAS DESIGNED FOR HVAC OR PROVIDE STRUCTURAL CALCULATIONS.
09/06/2005 ROBERT SHERRY WATER REVIEW Approved
09/06/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
09/06/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Specify the R-value for the duct insulation.
2. The use of ASHRAE 62n for ventilation calculations has not yet been adopted by the COT. Calculate the ventilation ising Section 403, IMC 2000 or submit an appeal to the building official.
09/06/2005 DAVE MANN ELECTRICAL-COMMERCIAL REVIEW Approved
09/06/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/28/2005 KMEDINA1 WWM REVIEW Needs Review