Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM04559
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | need to show sewer connection to hcs not septic. need drawing showing HCS location or man hole tap permit |
| 11/21/2005 | NEAL SAUNDERS | BUILDING-RESIDENTIAL | REVIEW | Denied | 1. 13/6 - Specify ledger to parapet wall connection. 2. Roof trusses over B9. Detail was not provided. Also trusses E1 and D1 require 5.5" of bearing each, yet B9 is a 3-1/8"x10" GLB, thus only providing 3-1/8" of bearing. Clarify. 3. Roof Plan shows parapet between kitchen and laundry. Return comments note 'Parapet on top of girder truss', yet a girder truss has not been shown at this location on roof framing or in truss calcs. Clarify. 4. Tower section cut B/7 shows truss G1 on a hanger while truss calcs require 5.5" of bearing. Clarify. 5. Plumbing plan - any 2003 IRC references must be removed. 6. Gas - Provide total developed length (meter to furthest appliance), which I assume will be the pool heater. Provide a complete summary of gas appliances - Include BTU for furnaces (100kx2) and pool heater (400k) and provide total. Pipe sizing seems adequate depending on length from house to pool heater. 7. Water line - Hose bibbs must be included at 3 f.u. each. Therefore total fixture units should be 41 (3 hose bibbs shown). 8. Obtain zoning and engineering approvals on new site plan at next submittal. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/23/2005 | DELMA ROBEY | OUT TO CUSTOMER | Completed |