Permit Number: T05CM04559
Parcel: 133032230

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04559
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2005 GERRY KOZIOL WWM REVIEW Denied need to show sewer connection to hcs not septic.
need drawing showing HCS location or man hole tap permit
11/21/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied 1. 13/6 - Specify ledger to parapet wall connection.

2. Roof trusses over B9. Detail was not provided. Also trusses E1 and D1 require 5.5" of bearing each, yet B9 is a 3-1/8"x10" GLB, thus only providing 3-1/8" of bearing. Clarify.

3. Roof Plan shows parapet between kitchen and laundry. Return comments note 'Parapet on top of girder truss', yet a girder truss has not been shown at this location on roof framing or in truss calcs. Clarify.

4. Tower section cut B/7 shows truss G1 on a hanger while truss calcs require 5.5" of bearing. Clarify.

5. Plumbing plan - any 2003 IRC references must be removed.

6. Gas - Provide total developed length (meter to furthest appliance), which I assume will be the pool heater. Provide a complete summary of gas appliances - Include BTU for furnaces (100kx2) and pool heater (400k) and provide total. Pipe sizing seems adequate depending on length from house to pool heater.

7. Water line - Hose bibbs must be included at 3 f.u. each. Therefore total fixture units should be 41 (3 hose bibbs shown).

8. Obtain zoning and engineering approvals on new site plan at next submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/23/2005 DELMA ROBEY OUT TO CUSTOMER Completed