Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T05CM04535
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/07/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/30/2005 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS for Activity # T05CM04535 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. FOUNDATION PLANS: 1. Note and specify appropriate double underlayment material for the low-slope asphalt shingle roof, R905.2.2. STRUCTURAL PLANS: 1. Provide manufacturer's calculations and data for pre-fabricated trusses, or note the requirement for deferred submittal to building inspector at installation. 2. Specify the gable end bracing and connections to the structure. 3. Locate braced panels not to exceed 25' o/c (west wall) with the appropriate nailing schedule (8d @ 6" o/c edge & @12" o/c field), R602.10.6. SECTIONS - DETAILS - MISC. NOTES: 1. Ceiling gypsum board shall be either 5/8" or ½" sag resistant when applied to 24" o/c framing, IRC table R702.3.5 footnote d. MECHANICAL PLANS: 1. Provide return air duct and register sizes, M1602.2. (heat pump / air conditioner - 6 sq. in. / 1000 BTU) (1ton cooling = 12,000 BTU) 2. Show dryer vent size and location M1501. ELECTRICAL PLANS: 1. Bathroom receptacles shall be on a separate 20 AMP circuit with no other outlets (circuit #15 is shown as 15 AMP), E3603.4. 2. All receptacle outlets serving kitchen countertops shall have ground fault circuit interrupting protection (note GFI at the outlet connected to circuit #18), E3802.6. 3. Indicate the location of all disconnect switches for air handling equipment circuit #1/3. 4. Clarify the location of circuit #20. 5. Indicate the wire and breaker size for circuit #13. MODEL ENERGY CODE: 1. Clarify the MEC entries. Provide energy calculations per the 2000 IECC w/ local amendments (climate zone 4B, 2100 HDD) complying with 2003 IRC chapter 11. http://www.energycodes.gov/rescheck/ 2. Show the "R" values of insulation, as well as the "U" values of the windows in compliance with the energy calculations provided. If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/12/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 10/12/2005 | SUE REEVES | REJECT SHELF | Completed |