Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T05CM04526
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2005 GERRY KOZIOL WWM REVIEW Denied site does not match data base, see attached. parcel shown is 140-23-117B. parcel with this address is 140--23-117A. need correct valid address.
10/18/2005 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T05CM04526

10/21/05 5935 S. MORRIS BLVD.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. PLEASE CHECK THE 1" WATER LINE FROM THE WATER METER . IT APPEARS TO BE UNDER SIZED.

FOUNDATION PLANS:

1. PLEASE JUSTIFY NOTE 3 FOR THE GARAGE FOOTING. IS THIS A "TYPO"?

2. PLEASE PROVIDE A LANDING FOR THE GARAGE 3068. SEE R311.4.3 .

3. ALL FOUNDATION HOLD-DOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED AND
LOCATED.

FLOOR PLANS:

1. PLEASE REMOVE NOTES #2 AND #6 IF THEY AREN'T USED.

2. PLEASE SPECIFY SAFETY GLASS FOR THE PORTION OF THE 8050 XO THAT IS WITHIN 2 FEET OF THE DOOR.

3. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

4. PLEASE SPECIFY THE WALL COVERING ON THE GARAGE SIDE OF THE WALL COMMON WITH THE LIVING AREA.

5. LOCATE AND IDENTIFY SHEAR WALL TYPES AND LOCATIONS. PROVIDE NAILING SCHEDULE.





STRUCTURAL PLANS:

1. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

ELEVATIONS:

1. NORTH ELEVATION / 5 ; ONE OF THE WINDOWS IS LABELED AS A DOOR.

2. SOUTH ELEVATION / 5 ; A 6" X 8" GRILL DOESN'T APPEAR TO PROVIDE THE 50 SQUARE INCHES, NET, REQUIRED BY TABLE 5-A UPC AMENDMENTS FOR A WATER HEATER.

SECTIONS - DETAILS - MISC. NOTES:

1. 1 / 2 ; OF THE "CB" SERIES POST BASES THE "CBSQ" IS THE ONLY ONE THAT WILL RAISE THE END GRAIN 1" ABOVE THE FLOOR. WILL THE POST BASE BE A "CBSQ" OR WILL THE POST BE PRESSURE TREATED OR OF A NATURAL RESISTANCE TO DECAY?

2. 3 / 2 ; THIS APPEARS TO BE FROM A METAL BUILDING. DO YOU WANT THIS DETAIL WITH THE SIDING RECESS AND THE METAL BUILDING NOTATION? IF NOT, PLEASE PROVIDE A CROSS SECTION OF A TYPICAL FOOTING.

3. 2 / 4 ; PLEASE SPECIFY SAG-RESISTANT FOR ½" GYPSUM WALL BOARD ON CEILINGS FRAMED AT 24" O.C. SEE TABLE R702.3.5 D .

4. PLEASE CLARIFY NOTES 2, 3, 4, 5, AND 9 ON SHEET 4 TO THE LEFT OF THE FRAMING PLAN.

5. GENERAL NOTES: (*) / 5 ; PLEASE SPECIFY 8d COMMONS TO NAIL THE ROOF DIAPHRAM OR JUSTIFY THE 6d. SEE TABLE R602.3(1).

PLUMBING PLANS:

1. 1 /6 ; ALL OF THE WATER DISTRIBUTION IS ½" AND APPEARS TO BE UNDERSIZED.

2. THE PLUMBING PLAN SHOWS A 4" LINE REDUCING TO A 3" LINE AND THEN OPENING UP AGAIN TO A 4". 3" APPEARS TO BE ADEQUATE BUT IF 4" IS USED IT CAN'T BE RESTRICTED TO 3" .

3. SEWER ISOMETRIC / 6 ; THE EVAPORATIVE COOLER DRAINING INTO THE CLOTHES WASHER VTR CREATES A WET VENT BETWEEN TWO LEVELS AND IS PROHIBITED. SEE UPC 908.1 .

4. PLEASE REMOVE THE IRC PLUMBING REFERENCES.

5. ¾" GAS LINE APPEARS TO BE INADEQUATE TO PROVIDE 170 CFH @ 65 LINEAL FEET. ISOMETRIC DOESN'T MATCH FLOOR PLAN.

6. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

MECHANICAL PLANS:

1. MECHANICAL NOTE1 / 7 ; 8" X 6" GRILL DOESN'T APPEAR TO PROVIDE 50 SQUARE INCHES, NET, COMBUSTION AIR FOR THE WATER HEATER.

2. PLEASE PROVIDE COMBUSTION AIR FOR THE FURNACE. NOTE #8 ?

ELECTRICAL PLANS:

1. THE NOTE AT THE BOTTOM OF THE LOAD CALCULATIONS SPECIFIES A 65 AMP SERVICE WHICH IS LESS THAN THE 100 AMP MINIMUM. BUT THE SERVICE SPECIFIED AT THE TOP OF THE PANUL SCHEDULE IS A 200 AMP SERVICE. WHICH SERVICE WILL BE USED?

2. PLEASE PROVIDE A SWITCHED LIGHT OUTSIDE THE GARAGE'S 3068. SEE E3803.3 .

3. PLEASE CLARIFY "SOR" @ THE RECEPTACLE IN THE BATHTUB.

4. PROVIDE A RECEPTACLE FOR THE FURNACE.

5. PROVIDE "OUTDOOR LIGHTING CODE" CALCULATIONS OR SPECIFY FULL CUT OFF LIGHT FIXTURES.

6. PLEASE PUT THE SMOKE DETECTORS AND THE EVAPORATIVE COOLER ON SEPARATE CIRCUITS.

7. ELECTRIC RISER DIAGRAM / 8 ; THE 3/0 SERVICE ENTRY CABLES WILL SUPPLY ONLY ONE 200 AMP SERVICE, BUT WHAT EVER THEY END UP BEING WILL BE SUPPLIED BY TEP AND WILL MEET THEIR SPECIFICATIONS.




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

PLEASE READ WASTE WATER'S COMMENTS.