Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
08/30/2005 JIM EGAN FIRE REVIEW Approved
08/30/2005 ANY ENGINEERING REVIEW Approved
08/31/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04509 8/31/05

1. Provide Structural Calculations for pole and foundation design, designed and sealed by a Structural Engineer, registered in the State of Arizona.
2. Specify conduit and conductor size and type.
3. Clarify 20 pole, 220V CB.
4. Provide Available Fault Current.
5. Specify fault current rating of new panel.
6. Specify feeder overcurrent protective device.
7. Provide a Single Line diagram of the service, grounding electrode system, and all new and existing panels and feeders.
8. Indicate Special Inspection per Tucson Lighting Code 8.1 7.