Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM04506
Parcel: 135074640

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04506
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculations and a design for the water supply to the restroom. Reference Section 610.1, UPC 1994.
2. Revise the size of the trap and trap arm from the lavatory to a maximum of 1-1/2". Reference Table 7-3 footnote, UPC 1994.
3. Revise the length of the trap arm for the lavatory to a maximum of 3'-6" (for 1-1/2" trap arm). Reference Section 1002.2, UPC 1994.
4. Specify the fixtures and fittings to be installed.
08/30/2005 ROBERT SHERRY WATER REVIEW Approved
08/30/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation for the restroom that complies with the requirements of Section 403.3, IMC 2000.
09/06/2005 DROBEY1 FIRE REVIEW Needs Review
09/06/2005 GERRY KOZIOL WWM REVIEW Approved
09/06/2005 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
09/06/2005 DROBEY1 ZONING REVIEW Needs Review
09/06/2005 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
09/06/2005 DROBEY1 ENGINEERING REVIEW Needs Review