Review Status: Completed
Review Details: OTHER
Permit Number - T05CM04503
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/30/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/30/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 09/02/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | t05cm04503 8/30/05 1. Add load on Ckt D-6. 2. Provide power for microwave Keynote 10 Power Plan. 3. Keynote 16 & 15 Power Plan single phase, 3-phase on panel schedule. 4. Since New Panel C is 200A, it does not appear logical to power it from a 100A disconnect with a 80AF. 5. Specify the line side and load side series rated devices. |